Thank you for taking interest in the Westinghouse Electric Corp part number S1532392, a Circuit Breaker product that we stock that is presented alongside the NSN 5925-00-159-0444 for ease of identification. If you would like to learn more about this component and secure purchasing options for your consideration, please fill out and submit the Request for Quote (RFQ) form that is offered below. All we ask is that you supply us with enough information to best accommodate any particular requirements or restrictions that you may have, and we will respond with a curated quote within 15 minutes of our receipt and review.
Note : We Will Not Share Your Information To Any Third Parties.
We strive to ensure that customers only receive precise items of need, opting to arrange our collection by diverse, commonly recognized forms of data. For instance, part number S1532392 specifically traces back to Westinghouse Electric Corp through the CAGE Code 79500, a distinct identifier for one of their physical locations. Moreover, with the NSN 5925-00-159-0444, this listing falls within Federal Supply Code (FSC) 5925 Circuit Breakers, enabling one to figure out its basic application. Keeping this in mind, do not hesitate to obtain a competitive quote for part number S1532392 here on Aero OEM Parts at your earliest convenience.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-159-0444 Item PartTypeName: CIRCUIT BREAKER | 5925 | 001590444 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
S1532392 | 1 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
CWJK | CASE MATERIAL | PLASTIC |
FEAT | SPECIAL FEATURES | MTG HOLES IN 2 ROWS OF 3,1.375 BY 4.844 IN. C TO C |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
ABHP | OVERALL LENGTH | 6.000 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 3.969 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 4.125 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
APNQ | ARC QUENCHING METHOD | DEION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC AND 15.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 125.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 210.000 MINIMUM AND 4200.000 MAXIMUM ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 210.000 MINIMUM AT 125 PCT AND 4200.000 MAXIMUM AT 125 PCT AND 20.000 MINIMUM AT 200 PCT AND 105.000 MAXIMUM AT 200 PCT AND 8.000 MINIMUM AT 300 PCT AND 23.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |